3) An air conditioner is used to cool and dehumidify air. Wewill ignore the temperature
aspect and model the air conditioner as a partial condenser. Humidair can be considered
a mixture of two components: dry air and water vapor. Fresh feedair containing 3.00%
water entering at a rate of 50.0 kg/min is mixed with a recyclestream of previously dehumidified air. All compositions aremeasured by mass. The mixture enters a
condenser that removes a portion of the water in one stream (aspure liquid water). The
second stream exiting the condenser contains air of lower humidity,specifically 1.50%
water. 70.0% of that air is recycled, as mentioned earlier, and therest is delivered to a
house.
(A) Carefully and completely label the flowchart for thisprocess.
(B) Calculate the rate of water removal from the condenser, therate of dehumidified
(1.50% water) air delivered to the house, and the flow rate andcomposition of the humid
air entering the condenser